C3 / C4

Protect

Condenser coil sensor seating

T3 reads implausible vs T4 (T3 < T4 − 3°F for 10 min).

Walk C3 / C4 in Diagnose

Sign in for the next measurement

First check

1 Which sensor is this code?

On Bosch BOVA 2.0 C3 / C4 is a specific thermistor — indoor return/pipe, outdoor coil, discharge, or ambient. Unplug that sensor and ohm it vs the OEM temperature/resistance chart. T3 on the outdoor coil U-bend per the diagram, not hanging in air.

Expect: Ohms move with temperature. Not open, not shorted.

The rest of the walkthrough is Diagnose.

On the plates

  • T3 on the outdoor coil U-bend per the diagram, not hanging in air.
  • T3/T4 10K ohms. 18 SEER has one T3; some 15/20 SEER have T3 and T3L.