Amana
FE3 / LE4 / SE5 / rE6
HazardA2L mitigation
Leak / comm / relay alarm from the A2L board when paired with R-32 or R-454B outdoor.
Walk FE3 / LE4 / SE5 / rE6 in Diagnose
4 plates — walk the one on the cabinet
First check
1 Confirm this pair is actually A2L
On Amana AR9S80 FE3 / LE4 / SE5 / rE6-class codes are only valid when this furnace is tied to an R-32 or R-454B outdoor. On R-410A this is a miswired mitigation harness — not a leaking indoor coil.
Expect: Outdoor refrigerant from the outdoor nameplate, not from memory.
If fail: Remove / correct the mitigation harness. Do not condemn the IFC.
The rest of the walkthrough is Diagnose.
On the plates
- Only valid on A2L pairs. On 410A, this is a miswired mitigation harness.
- Leak sensor location, ventilation blower, and OEM mitigation sequence before you condemn the IFC.
- Only valid on A2L pairs. On 410A this is a miswired mitigation harness.
- This is Category I metal vent. There is no 96% collector or PVC trap to prime.
- Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Plates that use FE3 / LE4 / SE5 / rE6
Same number, other makers
FE3 / LE4 / SE5 / rE6 on Amana is not the same code on these plates.