Amana
Ed
HazardOpen rollout
Manual-reset rollout opened. Treat as flame outside the exchanger until proven otherwise. Door chart may render this as a distinctive 7-seg character — confirm on the unit sticker.
Walk Ed in Diagnose
4 plates — walk the one on the cabinet
First check
1 Treat this as flame outside the exchanger
Do not reset the Amana AR9S80 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
The rest of the walkthrough is Diagnose.
On the plates
- Primary exchanger cracks, burner alignment, crossover.
- Blocked secondary / condensate / flue.
- Reset only after the cause is fixed. Recurring rollout is a CO / fire call.
- Primary exchanger, burner alignment, crossover, blocked flue / chimney.
- Reset only after the cause is fixed.
Plates that use Ed
Same number, other makers
Ed on Amana is not the same code on these plates.