Amana
Eb / Ec
LockoutGas valve circuit
Internal (Eb) or external (Ec) gas-valve electrical fault.
Walk Eb / Ec in Diagnose
4 plates — walk the one on the cabinet
First check
1 Coil ohms and 24 VAC during trial only
On Amana AR9S80 measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Valve coil ohms, 24 VAC at the harness during trial.
Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.
The rest of the walkthrough is Diagnose.
On the plates
- Valve coil ohms, 24 VAC at the harness during trial.
- Do not apply 24 V to a leaking valve as a ‘test’ and walk away.