Wiring

Packaged rooftop · heat pump 24V

R / C / Y1 / O-B / W-aux / G

Walk this circuit

Written landings stay open. Diagnose is the seat.

R / C / Y1 / O-B / W-aux / G

Packaged heat pump. RV is in this cabinet. Electric heat is aux. Economizer still steals the cool call on mild OA.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC. Packaged: Y1 may go to the economizer, not the contactor; VFD enable is 24V, speed is 0–10 V.

Open manufacturer wiring diagram

Cabinet sequence

  1. 1Power. Disconnect → transformer → RLine / 24V
  2. 2Fan. G → indoor blowerProve before defrost heat
  3. 3Cool/HP. Y1 → contactor; O/B → RV~24 VAC
  4. 4Aux. W → stripsElectric heat

24V packaged HP

Plate is 50FCQ / WSC / GPH / ZH class — no gas valve.

Thermostat / DDC

O/B is the RV. W is electric heat / defrost aux, not a gas valve.

  • R24V hot24V
  • CCommon24V
  • Y1Compressor24V
  • O/BReversing valve — confirm this controller’s silk24V
  • WElectric heat / aux24V
  • GIndoor fan24V

Unit controller

Defrost, economizer, and the RV relay live here.

  • Y outContactor through HPS24V
  • RVReversing-valve solenoid24V
  • AUXElectric heat24V
  • EN / 0–10Indoor VFD enable and speed, when this cabinet is a drive24V

Economizer

Still steals the cool call on mild OA. Same FDD sensors as the G/E cabinet.

  • ACTActuator 2–10 V or 24 V floating24V
  • OA TOutside-air sensor24V
  • MATMixed-air sensor24V

Landing

  • 24VY1contactor through HPS

    Compressor

  • 24VO/BRV solenoid

    Shift. No shift is not a charge call.

  • 24VWelectric heat kit

    Aux / defrost

Prove it

  • Y1 at the board.
  • O/B present on the call this silk uses.
  • Damper not stealing cool.

Do not

  • Do not look for an IGC on a 50FC / WSC / GPH.
  • Do not diagnose defrost with a split-system defrost board chart.

RV is in the packaged box. There is no outdoor unit on the ground.