Models
Bryantfurnace

880TA

Evolution 80% · two-stage · metal vent

Bryant Evolution 80% two-stage (current 880TA; 355CAV is the older Infinity-80 badge twin of Carrier 58CVA). Category I metal vent. No PVC collector. 31 is chimney/inducer, never a 96% trap. 355CAV door cards are an older IFC generation — confirm THAT sticker.

Not 926T / 916S condensing. A 31 here is metal-vent draft. Not 800S Legacy single-stage 80% (no ABCD). Not 987M.

AFUE

80% · Category I metal vent

Staging

Two-stage gas · two-speed inducer · metal-vent draft switch

Bus

Evolution ABCD on communicating SKUs

This board

Evolution / two-digit IFC (80% metal vent)

  • 13/33 limit, 14/34 ignition, 31 draft, 24 fuse — same numbers as 96% Bryant boards, different vent.
  • No secondary condensate path. Do not dump a ‘trap’ that is not there.
  • 355CAV / 355MAV older variable 80% — similar metal-vent 31, different IFC generation. Read that door card.

Evolution events or board last-status. Write the two digits first.

Universal swap

No universal

Evolution-family 80% two-stage. Treat as communicating until the silk proves HK42FZ017.

Silk: Evolution · HK42FZ017

White-Rodgers

ICM

  • ICM2807

    Only if the silk is HK42FZ017 and there is no Evolution ABCD bus. Uncommon on this plate.

Honeywell

  • Any 50A55-843 / 50A65-843 / 50M56U-843 / 50M56X-843 / S9200U1000 universal — those are conventional 24V HSI, not this data bus.
  • ICM280 / 2811 / 2810 / 282B — wrong IFC family.
  • 800S single-stage Comfort board. 50A55-843.

After you pull the dead card

  1. 1Photograph silk and wall control. Evolution UI → OEM Evolution IFC. HK42FZ017 only → ICM2807.

Field wiring

Written landings for Bryant 880TA. Not a factory schematic.

Infinity / Evolution furnace
ABCDGas furnace

59MN7 / 59TN6 / 987M / 986T class. Four-wire communicating furnace. D is 24V hot, not W and not Y.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC120V
  2. 2Call. Data pair or 24V W → IFCBus or 24V
  3. 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
  4. 4Ignite. IFC → HSI → valve120V igniter
  5. 5Blow. IFC → serial ECMNo tap, no cap

This indoor

Evolution 80% two-stage. Metal vent.

ABCD only

Infinity or Evolution wall control and a matching outdoor.

Infinity / Evolution control

A/B data, C common, D 24V hot.

  • ADataData
  • BDataData
  • C24V common24V
  • D24V hot — not W24V

Infinity / Evolution IFC

Same ABCD. Do not convert it to 24V by landing W and walking away.

  • ADataData
  • BDataData
  • CCommon24V
  • D24V hot24V

Landing

  • DataStat A/BIFC A/Boutdoor A/B

    Data

  • 24VStat C/DIFC C/D

    24V common / hot. D is not Y or W.

IFC harness — communicating two-stage

Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.

Transformer + fuse

24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.

  • L1 / N120VLine
  • R / C24V strip24V
  • FUSEOn the IFC24V

24V safety chain

Limit / rollout / door still open the heat path. Codes are on THIS IFC language.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + dual PS

Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.

  • IND LO/HITwo-speed inducerLine
  • LPSLow prove24V
  • HPSHigh prove24V

HSI + two-stage valve

Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.

  • HSI120V igniterLine
  • MV / HV24V low / high solenoids24V
  • FLAMEµA DC24V

Serial variable-speed ECM

IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.

  • SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
  • CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V

Landing

  • LineCallIFCinducerprove

    Low then high

  • LineIFCHSIvalve

    120V igniter, 24V or serial valve

  • 24VFlame rodIFC

    µA DC

  • DataIFCserial blower

    No F-taps. No PSC cap.

Prove it

  • Wall-control equipment list. The furnace and outdoor both present.
  • ABCD polarity. C still required.

Do not

  • Do not land W on a spare screw to make it 24V.
  • A 926T / 59TP6 / 59SC5 is the other diagram.

ABCD is the published Infinity / Evolution control.

Sequence

  1. 1

    Low

    Inducer → metal-vent prove → HSI → low fire. 31 if the chimney will not prove.

  2. 2

    High

    High fire, still Category I. Wind and shared chimneys show up here.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

24

Fuse

warn

24 V fuse.

  1. 1 Find the 24 V short before you replace the fuse

    On Bryant 880TA an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. ABCD miswire, HUM, valve.

    Expect: Fuse out. 24 V transformer still good. Harness isolated.

  2. 2 Replace the fuse with the harness off

    New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC).

    Expect: Fuse holds with harness off. Dies when the shorted lead lands.

  3. 3 If it blows with the harness off

    Short is on the Bryant 880TA IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.

    Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.

31

Draft / PS

lockout

Metal vent will not prove. Not a 96% trap.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Bryant 880TA active code. Write 31. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Chimney liner, cap, common-vent tables, inducer wheel.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. PS hose to the inducer housing can hold flue condensate on a long metal run — still Cat I.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

33 / 13

Limit

warn

Airflow. 80% A-coils still dirty.

  1. 1 Airflow before you touch the limit

    On Bryant 880TA a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, coil on top, blower, Evolution heat CFM. Rollout manual reset.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Bryant 880TA blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).

    Expect: Manifold on plate. Limit closed when cool.

34 / 14

Ignition

lockout

HSI / gas / rod.

  1. 1 Ohms at the igniter, then at the IFC

    On Bryant 880TA measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Fix 31 draft before a fair 34 test.

    Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

ABCD

Communication

lockout

Wall control or outdoor dropped (communicating SKUs).

  1. 1 Data pair, not 24 V

    On Bryant 880TA indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. A/B/C/D, polarity, C, no 24V on D.

    Expect: Pair continuous, not shorted to chassis, polarity per the diagram.

  2. 2 Power both ends, then the outdoor status

    Indoor transformer and outdoor control both alive. Read the outdoor LED / 7-seg. Water in the outdoor control is the usual dead-end after a storm.

    Expect: Both controls powered. Outdoor showing a comm or address state, not a blank board.

  3. 3 Address / bias, then the control

    Communicating plates need a matching indoor address and sometimes a terminating bias. Swap is last: known-good pair + power both ends + correct address.

    Expect: Indoor sees the outdoor. No comm code after a power cycle.

Workflows

31 on 880TA / 355CAV

Do not cut a condensate trap.

  1. 1 Prove the call and the live code

    This furnace has no secondary drain. Look at the metal vent and the inducer wheel.

    Expect: Write whatever Evolution / two-digit IFC (80% metal vent) is showing. Evolution events or board last-status. Write the two digits first.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Common-vented water heater: venting table / liner, not a switch.

    Expect: High: High fire, still Category I. Wind and shared chimneys show up here.

  3. 3 Confirm with a number, then the next part

    Then the PS hose on the inducer housing.

    Expect: Vent: Cat I tables. Spillage at the draft hood / inducer inlet is a fail.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Vent

Cat I tables. Spillage at the draft hood / inducer inlet is a fail.

Gotchas

  • 355CAV is the older Bryant Infinity 80 you will see in basements. 880TA is the current Evolution 80. Same metal-vent 31 idea; confirm the door card.
  • Carrier 58CVA is the factory twin of 355CAV.

Related plates

Install this plate

Install 880TA / 355CAV as Evolution 80% two-stage. Metal vent + ABCD — no PVC trap.

Cat I metal vent · two-stage 80% · Evolution ABCD · 31 is chimney/draft, not a collector

Vent

  • Category I. B-vent / listed liner / common vent. There is no 96% trap to prime.
  • 31 is metal-vent draft. Dumping condensate that is not there will not clear it.

Bus

  • Evolution ABCD. Carrier 58CVA is the factory twin of 355CAV.
  • 800S is the 24V Legacy 80% cousin — same metal vent, no ABCD.

First fire

  1. 1Pair Evolution, then a heat call. Draft switch / 31 must close on a legal Cat I vent.
  2. 2CO / spillage check at the draft hood. Stop if it spills.

Do not on Bryant 880TA

  • Do not glue PVC to this flue.
  • Do not apply 926T trap / collector steps to a 31 here.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • 880TA product pageProduct pageOpen manufacturer PDF
  • Bryant document searchLiterature searchEnter the full Bryant plate (926TB60100V21, 987MA…). Owner PDFs are public; many I/Os are dealer-gated.Open manufacturer PDF
  • Bryant document searchLiterature searchSearch Bryant 880TA on the maker’s literature page.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    warranty sheet

    Carrier / Bryant registered heat-exchanger terms

    Current 59-series / Evolution / Preferred registered warranty · Limited warranty certificate

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal