Economizing when it should not

Damper open with OA above changeover. Space hot, high OA bills, or wet coil.

Walk False econ in Diagnose

Sign in for the next measurement

First check

1 Damper position vs command

On York ZF look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. OA vs changeover setpoint. Sensor lying low (see OA T) is the usual.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

The rest of the walkthrough is Diagnose.

On the plates

  • OA vs changeover setpoint. Sensor lying low (see OA T) is the usual.
  • Min position cranked to 40% on a small store. DCV failed high.
  • Power-fail default on some actuators is spring-open — they dump OA with 24 V lost.