York
Econo
ProtectEconomizer FDD
Start here when the hood is the complaint. Title 24 FDD classes: sensor, not-economizing, false-economizing, damper not modulating, excess OA.
Walk Econo in Diagnose
Sign in for the next measurement
First check
1 Damper position vs command
On York ZF look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Read the module in THIS hood (JADE W7220 / W7212 / Reliatel / Prodigy / factory FDD). Type the live LCD string — examples: MA SENS ERR, OA SENS ERR, CO2 SENS ERR, ACT ERROR.
Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.
The rest of the walkthrough is Diagnose.
On the plates
- Read the module in THIS hood (JADE W7220 / W7212 / Reliatel / Prodigy / factory FDD). Type the live LCD string — examples: MA SENS ERR, OA SENS ERR, CO2 SENS ERR, ACT ERROR.
- Blade vs command first. Then OA / RA / MAT vs a real thermometer. Then Y1 vs compressor.
- Do not add refrigerant because mixed air is cold — that is often the damper.
Plates that use Econo
Same number, other makers
Econo on York is not the same code on these plates.