York
Charge
ProtectCharge (SH piston / SC TXV)
Wrong charge method is as common as wrong charge.
Walk Charge in Diagnose
3 plates — walk the one on the cabinet
First check
1 Airflow and freeze before you add gas
On York YC2E low pressure / freeze is indoor airflow or a starved coil until proven otherwise. Filter, blower, dirty A-coil, closed supplies. In heat mode, a iced outdoor coil is the same family. Indoor piston: charge by superheat. Indoor TXV: charge by subcooling.
Expect: Indoor air moving. Coil not iced. OD coil clear in heat.
The rest of the walkthrough is Diagnose.
On the plates
- Indoor piston: charge by superheat. Indoor TXV: charge by subcooling.
- Do not use Greenspeed weigh-in-only as the only method unless the factory TXV rating plate on THIS outdoor says so. Most 24ACC are piston/TXV conventional.
- Line-set length and indoor coil match still matter. Weigh-in after a repair, then finish on SH or SC.
Plates that use Charge
YXT
Affinity · two-stage mid
Diagnose YXT — Sign in
Same number, other makers
Charge on York is not the same code on these plates.