Trane
E5.x
HazardUnexpected flame / flame sense family (door-card confirm)
Flame-sense or unexpected-flame family. Confirm the exact decimal and OEM line on THIS S9V2 door card / service facts.
Walk E5.x in Diagnose
2 plates — walk the one on the cabinet
First check
1 Shut the gas cock first
On Trane S8V2 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Unexpected flame: shut the cock. Leaking valve is a hazard — do not jump it.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
The rest of the walkthrough is Diagnose.
On the plates
- Unexpected flame: shut the cock. Leaking valve is a hazard — do not jump it.
- No / weak prove: rod µA, ground, nitride, valve 24 VAC during trial.
- Do not map these to Amana E4/E6 or Carrier 22/34 by number.