Trane
E4.1
ProtectOpen reverse-airflow limit
Trane S9V2 alarm table: reverse-airflow limit is open.
Walk E4.1 in Diagnose
2 plates — walk the one on the cabinet
First check
1 Airflow before you touch the limit
On Trane S8V2 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Multi-poise cabinet — find the reverse-airflow switch for THIS orientation (blower-inlet / opposite the heat exchanger).
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
The rest of the walkthrough is Diagnose.
On the plates
- Multi-poise cabinet — find the reverse-airflow switch for THIS orientation (blower-inlet / opposite the heat exchanger).
- VS heat CFM in the IFC menu (no dips). Filter, coil, return. Rise vs plate.
- A missing or unplugged reverse-airflow jumper/switch on a converted orientation throws E4.1 with a cold exchanger.
- Other limit / rollout decimals — confirm on THIS S9V2 door card / service facts. Do not invent E4.2 / E4.3 titles.