Trane
E3.3
LockoutShorted second-stage pressure switch
Trane Link-enabled alarm table: second-stage PS is shorted / already made when the IFC expected it open.
Walk E3.3 in Diagnose
2 plates — walk the one on the cabinet
First check
1 Unplug the switch with the inducer off
On Trane S8V2 this code is the switch made when the inducer is not running. Unplug that switch only. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
The rest of the walkthrough is Diagnose.
On the plates
- Unplug the second-stage switch. If the code changes, switch/hose. If not, IFC input.
- W2 shorted to W1 can keep the high-fire path made. Confirm the call.
- Two switches, two hoses. A tee is a miswire.
- This is Category I metal vent. There is no 96% collector or PVC trap to prime.
- Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.