Trane
Comm / data pair
LockoutComfortLink indoor-outdoor drop
Stat, indoor, or outdoor off the bus. Outdoor silent while the indoor is calling is often this — or a dead drive. Check bus vs drive LEDs before you gauge.
Walk Comm / data pair in Diagnose
2 plates — walk the one on the cabinet
First check
1 Let it cool, then read the drive LED
On Trane XV18 overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. Data pair landing and polarity at outdoor, indoor, and stat. No 24V on the pair.
Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.
The rest of the walkthrough is Diagnose.
On the plates
- Data pair landing and polarity at outdoor, indoor, and stat. No 24V on the pair.
- Outdoor board powered (line voltage). Comm LED vs inverter-fault LED — they are different stories.
- Isolate: indoor-only bus, then add outdoor. A cooked drive can take the whole ComfortLink down.
Plates that use Comm / data pair
Same number, other makers
Comm / data pair on Trane is not the same code on these plates.