Rheem
45 / 57
LockoutDraft at a firing rate
Modulating inducer / pressure did not prove at the commanded %. Not a simple two-switch tee like R96TA or the VA 45/46 split.
Walk 45 / 57 in Diagnose
2 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the Rheem R98MV active code. Write 45 / 57. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Vent, trap, collector, inducer throughout the rate, pressure hose / transducer path.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Vent, trap, collector, inducer throughout the rate, pressure hose / transducer path.
- Do not replace ‘the low PS’ off an R96TA card.
- Watch whether the fault appears only at higher % — that is vent capacity, not a dead switch.