Pressure protect
LockoutHigh / low pressure protect
Outdoor high- or low-pressure protection (token is on the MXZ door card for this revision — do not invent a City Multi number).
Walk Pressure protect in Diagnose
Sign in for the next measurement
First check
1 Airflow and freeze before you add gas
On Mitsubishi MXZ-SM low pressure / freeze is indoor airflow or a starved coil until proven otherwise. Filter, blower, dirty A-coil, closed supplies. In heat mode, a iced outdoor coil is the same family. Service valves open. Outdoor fan. All indoor blowers that are calling.
Expect: Indoor air moving. Coil not iced. OD coil clear in heat.
The rest of the walkthrough is Diagnose.
On the plates
- Service valves open. Outdoor fan. All indoor blowers that are calling.
- Weigh-in + adders. Do not ‘top off’ to a piston SH chart.
- Restriction / drier / one indoor EEV stuck.