Lennox
RA ERR
ProtectRA SENS ERR (JADE LCD example)
JADE LCD: RA / SENS ERR. Return-air thermistor failed. Differential / enthalpy changeover compares OA to RA.
Walk RA ERR in Diagnose
2 plates — walk the one on the cabinet
First check
1 Damper position vs command
On Lennox LGH look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Probe RA in the return vs the module.
Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.
The rest of the walkthrough is Diagnose.
On the plates
- Probe RA in the return vs the module.
- A missing RA sensor on a differential setup looks like false economizing.
Plates that use RA ERR
Same number, other makers
RA ERR on Lennox is not the same code on these plates.