Lennox
Excess OA
ProtectExcess outdoor air
Damper open past the commanded minimum with no economizer or DCV request.
Walk Excess OA in Diagnose
2 plates — walk the one on the cabinet
First check
1 Damper position vs command
On Lennox LGH look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Commanded position vs blade. Feedback saying 80% when the board asked 15% is actuator/linkage.
Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.
The rest of the walkthrough is Diagnose.
On the plates
- Commanded position vs blade. Feedback saying 80% when the board asked 15% is actuator/linkage.
- Barometric relief / power exhaust stuck open looks like excess OA at the space.
- Unoccupied damper should go to the unoccupied minimum, often 0. A 24 V occupancy point stuck high holds min all night.