Lennox
1 flash
HazardUnexpected flame
Flame with the valve off.
Walk 1 flash in Diagnose
3 plates — walk the one on the cabinet
First check
1 Shut the gas cock first
On Lennox ML180 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
The rest of the walkthrough is Diagnose.
On the plates
- Shut the cock. Leaking valve.
Plates that use 1 flash
Same number, other makers
1 flash on Lennox is not the same code on these plates.