ProtectNot economizing when it should
OA is in the free-cooling window and the damper stayed shut. Title 24 FDD class.
Walk Not econ in Diagnose
Sign in for the next measurement
First check
1 Damper position vs command
On ICP PGC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Confirm OA really is below the high-limit / enthalpy changeover on THIS module (not a 55 °F guess).
Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.
The rest of the walkthrough is Diagnose.
On the plates
- Confirm OA really is below the high-limit / enthalpy changeover on THIS module (not a 55 °F guess).
- Y1 present? Some modules will not economize without a cool call.
- Min-position only, jammed blades, or a MAT low-limit holding the damper closed.
- Mechanical cool running in 50 °F OA is this fault until the damper moves.