ProtectPressure switch
Inducer ran (or should have) and the draft switch did not make.
Walk PS in Diagnose
Sign in for the next measurement
First check
1 Prove inducer and the live code
Do not pull power — that clears the Goodman GPG16 active code. Write PS. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer spinning. Wheel packed with rust / nest.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Inducer spinning. Wheel packed with rust / nest.
- Hose on the inducer tap, not cracked, not full of water. Roof units collect condensate in the hose.
- Flue / heat-exchanger restriction. Birds and insulation in the collector are a rooftop classic.
- Switch ohms with inducer forced. Do not leave it jumped.
Plates that use PS
Same number, other makers
PS on Goodman is not the same code on these plates.