Goodman
oC
LockoutoC / OC — overcurrent
Keypad example: oC (Yaskawa) or OC. Output current trip. Locked rotor, dirty filters, or FLA set too low.
Walk oC in Diagnose
Sign in for the next measurement
First check
1 Read the drive before you cycle power
On Goodman GPG16 photograph the VFD keypad or the unit-board fan alarm (OC, LU, OU, GF, OH, limp). Power-cycle wipes what you needed. Spin the wheel by hand (power off). Debris, seized bearing, belt wrapped.
Expect: Live drive code written down. Line voltage at L1/L2/L3 of the drive.
The rest of the walkthrough is Diagnose.
On the plates
- Spin the wheel by hand (power off). Debris, seized bearing, belt wrapped.
- Total external static vs this blower table. A rooftop with 1.4" TES and a 0.8" motor is an oC waiting to happen.
- FLA / motor-data parameters vs the motor nameplate. Do not raise FLA to hide a dirty coil.
- Ramp-up too fast on a high-inertia wheel — lengthen accel before you change a drive.
Plates that use oC
Same number, other makers
oC on Goodman is not the same code on these plates.