Goodman
Limit
ProtectLimit / aux limit
Heat-exchanger or supply limit opened.
Walk Limit in Diagnose
Sign in for the next measurement
First check
1 Airflow before you touch the limit
On Goodman GPG16 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filters, belt, blower rotation (3-phase indoor motors reverse).
Expect: TES / static: External static vs the blower table for this tonnage — rooftops run dirty.
The rest of the walkthrough is Diagnose.
On the plates
- Filters, belt, blower rotation (3-phase indoor motors reverse).
- Rise vs the rating plate. Overfire and low CFM look the same from the roof.
- Heat-section panel gasket / blocked return in the curb.
Plates that use Limit
Same number, other makers
Limit on Goodman is not the same code on these plates.