Goodman
EAF / EAL / EAS / Ear
HazardA2L mitigation
Leak / comm / relay alarm from the A2L board when paired with R-32 or R-454B outdoor.
Walk EAF / EAL / EAS / Ear in Diagnose
Sign in for the next measurement
First check
1 Confirm this pair is actually A2L
On Goodman GR9S96 FE3 / LE4 / SE5 / rE6-class codes are only valid when this furnace is tied to an R-32 or R-454B outdoor. On R-410A this is a miswired mitigation harness — not a leaking indoor coil.
Expect: Outdoor refrigerant from the outdoor nameplate, not from memory.
If fail: Remove / correct the mitigation harness. Do not condemn the IFC.
The rest of the walkthrough is Diagnose.
On the plates
- Only valid on A2L pairs. On 410A this is a miswired mitigation harness.