Goodman
E11
HazardOpen rollout
Display is E 1 1 — not EE1 (PS closed). Manual-reset rollout. Treat as flame outside the exchanger until proven otherwise.
Walk E11 in Diagnose
Sign in for the next measurement
First check
1 Treat this as flame outside the exchanger
Do not reset the Goodman GR9S96 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
The rest of the walkthrough is Diagnose.
On the plates
- Primary exchanger, burner alignment, crossover, blocked secondary / condensate / flue.
- Reset only after the cause is fixed.