Goodman codes

Goodman

E10

Lockout

Grounding error

IFC failed its ground check (sister to EEA).

Walk E10 in Diagnose

Sign in for the next measurement

First check

1 Hot and neutral at the IFC, not the disconnect

On Goodman GR9S96 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Green ground to cabinet and IFC. Painted screw, missing star washer.

Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

The rest of the walkthrough is Diagnose.

On the plates

  • Green ground to cabinet and IFC. Painted screw, missing star washer.