Goodman codes

Goodman

Contactor

Lockout

No start / hum

Y1 at the board, compressor not running.

Walk Contactor in Diagnose

Sign in for the next measurement

First check

1 Is Y actually at the contactor?

On Goodman GPG16 a silent outdoor is often no Y. Measure 24 VAC coil-to-C at the contactor on a cool call. 24 VAC across the coil. Then dual cap (if this chassis has one) or VFD / two-stage unload.

Expect: ~24 VAC at the coil when the indoor is calling.

If fail: Indoor Y / IFC / stat — not a capacitor.

The rest of the walkthrough is Diagnose.

On the plates

  • 24 VAC across the coil. Then dual cap (if this chassis has one) or VFD / two-stage unload.
  • 3-phase: phase loss, reverse rotation. A scroll run backwards is loud and pumps no gas.
  • Internal overload. Let it cool; find why it overheated.

Plates that use Contactor

Same number, other makers

Contactor on Goodman is not the same code on these plates.