Goodman
Contactor
LockoutNo start / hum
Y1 at the board, compressor not running.
Walk Contactor in Diagnose
Sign in for the next measurement
First check
1 Is Y actually at the contactor?
On Goodman GPG16 a silent outdoor is often no Y. Measure 24 VAC coil-to-C at the contactor on a cool call. 24 VAC across the coil. Then dual cap (if this chassis has one) or VFD / two-stage unload.
Expect: ~24 VAC at the coil when the indoor is calling.
If fail: Indoor Y / IFC / stat — not a capacitor.
The rest of the walkthrough is Diagnose.
On the plates
- 24 VAC across the coil. Then dual cap (if this chassis has one) or VFD / two-stage unload.
- 3-phase: phase loss, reverse rotation. A scroll run backwards is loud and pumps no gas.
- Internal overload. Let it cool; find why it overheated.
Plates that use Contactor
Same number, other makers
Contactor on Goodman is not the same code on these plates.