Daikin
U4
LockoutIndoor/outdoor comm
Data pair between this outdoor and the communicating indoor is down.
Walk U4 in Diagnose
Sign in for the next measurement
First check
1 Data pair, not 24 V
On Daikin DZ20VC indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. Polarity, gauge, splices on the data pair. This is not 24 V Y.
Expect: Pair continuous, not shorted to chassis, polarity per the diagram.
The rest of the walkthrough is Diagnose.
On the plates
- Polarity, gauge, splices on the data pair. This is not 24 V Y.
- Indoor must be communicating (DM96VC / AVPTC / AMVC / GMVC-class). GR9T96 / AR9T96 / 9-speed 24V cannot clear U4.
- One master. Leftover thermostat cable landed as ‘data’ will never train.
Plates that use U4
Same number, other makers
U4 on Daikin is not the same code on these plates.