Daikin
Hum / no start
LockoutCap / start
Compressor hums, outdoor fan may run.
Walk Hum / no start in Diagnose
2 plates — walk the one on the cabinet
First check
1 Is Y actually at the contactor?
On Daikin DC5SE a silent outdoor is often no Y. Measure 24 VAC coil-to-C at the contactor on a cool call. Dual cap (fan and herm). Replace on values, not just a bulge.
Expect: ~24 VAC at the coil when the indoor is calling.
If fail: Indoor Y / IFC / stat — not a capacitor.
The rest of the walkthrough is Diagnose.
On the plates
- Dual cap (fan and herm). Replace on values, not just a bulge.
- Hard-start only after the cap and windings are proven.
Plates that use Hum / no start
Same number, other makers
Hum / no start on Daikin is not the same code on these plates.