Bryant
ACT ERR
ProtectACT ERROR (JADE LCD example)
JADE LCD: ACT ERROR / ACT RANGE. Actuator did not follow command. Feedback pot off the shaft is the weekly.
Walk ACT ERR in Diagnose
Sign in for the next measurement
First check
1 Damper position vs command
On Bryant 581J look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Command min → 100%. 2–10 V (or 24 V floating) at the actuator vs blade travel.
Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.
The rest of the walkthrough is Diagnose.
On the plates
- Command min → 100%. 2–10 V (or 24 V floating) at the actuator vs blade travel.
- Linkage on the shaft. Seized blades. A 24 V actuator on a 2–10 V output.
Plates that use ACT ERR
Same number, other makers
ACT ERR on Bryant is not the same code on these plates.