Models
Yorkac

YXV

Affinity · inverter AC

York Affinity YXV inverter air conditioner. Outdoor drive. No reversing valve. Charge is weigh-in. Not YXT two-stage.

Not YXT two-stage. Not YC2E / YC2F LX. Not a York heat-pump YZF / YH (RV + defrost).

Drive

Inverter scroll · variable capacity

Bus

Affinity / Hx communicating when paired

Charge

Weigh-in + line-set

This board

Affinity outdoor inverter — AC only

  • Affinity events / outdoor drive.
  • No dual cap. No defrost.
  • YXT is the two-stage Affinity.

Affinity last events. Drive last-fault if the stat is blank.

Universal swap

No universal

York YXV outdoor. No furnace IFC universal. Replace the OEM outdoor control / contactor / drive by the silk.

Silk: YXV

White-Rodgers

ICM

Honeywell

  • Indoor furnace universals (50A55, 50M56U, ICM282B, ICM2811, S9200U). This is not an IFC.
  • Do not ‘adapt’ a furnace board to an outdoor inverter, defrost PCB, or contactor.

After you pull the dead card

  1. 1Photograph the outdoor silk. Indoor 50A55 / ICM282B / S9200U do not belong here.
  2. 2Contactor units: replace the contactor / cap / HPS — there is no universal outdoor board.
  3. 3Inverter / communicating outdoors: OEM drive only. There is no White-Rodgers or ICM outdoor universal.

Field wiring

Written landings for York YXV. Not a factory schematic.

York Affinity inverter AC
Affinity / Hx communicating pairRead the nameplate

York YXV. Affinity communicating inverter. YC2E / YC2F are 24V LX. YXT is two-stage, not this drive.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

This indoor

Affinity / Hx indoor. YC2E Y/C is the wrong book.

Affinity pair

Affinity / Hx wall control and a matching indoor.

Affinity / Hx control

Communicating pair on the silk. Do not invent a pin number.

  • DATAAffinity / Hx pairData
  • R24V if the control needs it24V
  • CCommon24V

YXV outdoor drive

Photograph the outdoor comm silk. No dual cap.

  • DATAAffinity pair on the silkData

Outdoor line — inverter drive

208/230 into the drive. No contactor slam. DC bus can stay live after the disconnect.

  • L1Line to the driveLine
  • L2Line to the driveLine
  • GNDEquipment groundLine

Landing

  • DataControl pairindooroutdoor pair

    Data. Not Y.

  • LineL1 / L2drive

    208/230

Prove it

  • Affinity control lists the outdoor. Bus vs drive before gauges.
  • Read the outdoor silk for the pair.

Do not

  • Do not use the YC2E Y/C diagram on YXV.
  • Do not invent Hx3 pin numbers.

Affinity pair only — no unpublished York pinout.

Sequence

  1. 1

    Call

    Indoor requests capacity. Inverter ramps.

  2. 2

    Protect

    HPS / LPS / drive. No defrost.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

Comm

ABCD / outdoor drop

lockout

Drive or bus. Wall control loses the outdoor.

  1. 1 Let it cool, then read the drive LED

    On York YXV overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. ABCD landing and polarity, outdoor board power, inverter comms harness.

    Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.

  2. 2 Voltage and compressor windings

    Incoming voltage in range (this plate’s line-voltage code). Compressor windings even, no ground. A shorted compressor will kill a new drive. C still required at the wall control.

    Expect: Balanced windings. No winding to ground. Line voltage stable under load.

  3. 3 Charge and the drive last

    A starved or flooded compressor will overcurrent. Confirm SH/SC and charge weight. Only then condemn the inverter. Indoor must be Infinity-capable. A 24ACC6-style indoor pairing is the wrong mental model.

    Expect: Charge on the nameplate. Drive code gone after a cool-down and a clean coil.

HPS / LPS

Pressure protection

lockout

Still real on an inverter.

  1. 1 Let it cool, then read the drive LED

    On York YXV overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. Coil, fan, charge by weigh-in — you do not ‘top off’ a Greenspeed.

    Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.

  2. 2 Voltage and compressor windings

    Incoming voltage in range (this plate’s line-voltage code). Compressor windings even, no ground. A shorted compressor will kill a new drive. Outdoor fan that is actually the inverter-driven fan, not a dual-cap PSC motor.

    Expect: Balanced windings. No winding to ground. Line voltage stable under load.

  3. 3 Charge and the drive last

    A starved or flooded compressor will overcurrent. Confirm SH/SC and charge weight. Only then condemn the inverter. Do not use 24ACC6 piston superheat as the pass/fail.

    Expect: Charge on the nameplate. Drive code gone after a cool-down and a clean coil.

Inverter

Drive overcurrent / overheat

lockout

L5/L4-class faults on the drive.

  1. 1 Let it cool, then read the drive LED

    On York YXV overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. Compressor to ground, heat sink, supply voltage. Weigh-in vs nameplate.

    Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.

  2. 2 Voltage and compressor windings

    Incoming voltage in range (this plate’s line-voltage code). Compressor windings even, no ground. A shorted compressor will kill a new drive. These L-codes do not exist on 24ACC6. If you are looking at a contactor, you are on the wrong outdoor.

    Expect: Balanced windings. No winding to ground. Line voltage stable under load.

  3. 3 Charge and the drive last

    A starved or flooded compressor will overcurrent. Confirm SH/SC and charge weight. Only then condemn the inverter.

    Expect: Charge on the nameplate. Drive code gone after a cool-down and a clean coil.

Workflows

Silent YXV

Indoor calling, outdoor not ramping.

  1. 1 Prove the call and the live code

    Drive / Affinity events. No contactor to chase.

    Expect: Write whatever Affinity outdoor inverter — AC only is showing. Affinity last events. Drive last-fault if the stat is blank.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Weigh-in. Not a YC2E SH chart.

    Expect: Protect: HPS / LPS / drive. No defrost.

  3. 3 Confirm with a number, then the next part

    Plate YZF / YH = heat pump. Do not stay here.

    Expect: Charge: Recover and weigh. Nameplate + ounces/ft. Not piston SH. · ABCD: Communicating to the Infinity indoor / 59MN7 family. D is not Y.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Charge

Recover and weigh. Nameplate + ounces/ft. Not piston SH.

ABCD

Communicating to the Infinity indoor / 59MN7 family. D is not Y.

Drive

Inverter LEDs / last fault. No contactor coil 24 VAC test.

Gotchas

  • YXT is one letter away and is two-stage, not this drive.

Related plates

Install this plate

Install York YXV as Affinity · inverter AC.

Affinity · inverter AC

This plate — not the sister SKU

  • Not YXT two-stage. Not YC2E / YC2F LX. Not a York heat-pump YZF / YH (RV + defrost).
  • YXT is one letter away and is two-stage, not this drive.

Control on this outdoor

  • Affinity events / outdoor drive.
  • No dual cap. No defrost.
  • YXT is the two-stage Affinity.

Hardware

  • Drive: Inverter scroll · variable capacity
  • Bus: Affinity / Hx communicating when paired
  • Charge: Weigh-in + line-set

First fire

  1. 1Drive / Affinity events. No contactor to chase.
  2. 2Weigh-in. Not a YC2E SH chart.
  3. 3Plate YZF / YH = heat pump. Do not stay here.

Do not on York YXV

  • Not YXT two-stage. Not YC2E / YC2F LX. Not a York heat-pump YZF / YH (RV + defrost).
  • YXT is one letter away and is two-stage, not this drive.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • York residential gas furnacesLiterature searchTM9 / TM8 family listing (Coleman / Luxaire share the JCI IFC). UPGNet holds the I/O.Open manufacturer PDF
  • York / Bosch Home ComfortLiterature searchSearch York YXV on the maker’s literature page.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    dealer

    York furnace warranty

    Registered TM8 / TM9 furnace warranty · Dealer claims portal

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal