iComfort furnace
I+ / I−
SLP99V / SL297NV / EL296V communicating. iComfort S30/S40 on I+ and I−. Many EL296V jobs are still 24V — use that landing if RS wires are empty.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC120V
- 2Call. Data pair or 24V W → IFCBus or 24V
- 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
- 4Ignite. IFC → HSI → valve120V igniter
- 5Blow. IFC → serial ECMNo tap, no cap
iComfort communicating
S30/S40 and a communicating outdoor, or communicating indoor-only.
iComfort S30 / S40
R, C, I+, I−.
- R24V hot24V
- CCommon24V
- I+DataData
- I−DataData
iComfort IFC
E105 on a 24V-only job means data wires landed on RS terminals. Pull them.
- I+DataData
- I−DataData
- R24V24V
- CCommon24V
- W124V heat if used24V
Landing
- DataStat I+/I−IFC I+/I−outdoor
iComfort data
- 24VR and C at the stat
~24 VAC
EL296V as 24V
No iComfort outdoor. Conventional W1/W2/Y. Leave I+ / I− empty.
Two-stage 24V stat
Normal W1/W2/Y/G. RS / I+ unused.
- RHot24V
- CCommon24V
- W1Low fire24V
- W2High fire24V
- YCool24V
- GFan24V
Landing
- 24VStat W1/W2IFC W1/W2
Two-stage heat
- 24VStat YIFC Youtdoor Y
Cool
IFC harness — communicating two-stage
Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.
Transformer + fuse
24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.
- L1 / N120VLine
- R / C24V strip24V
- FUSEOn the IFC24V
24V safety chain
Limit / rollout / door still open the heat path. Codes are on THIS IFC language.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + dual PS
Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.
- IND LO/HITwo-speed inducerLine
- LPSLow prove24V
- HPSHigh prove24V
HSI + two-stage valve
Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.
- HSI120V igniterLine
- MV / HV24V low / high solenoids24V
- FLAMEµA DC24V
Serial variable-speed ECM
IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.
- SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
- CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V
Landing
- LineCallIFCinducerprove
Low then high
- LineIFCHSIvalve
120V igniter, 24V or serial valve
- 24VFlame rodIFC
µA DC
- DataIFCserial blower
No F-taps. No PSC cap.
Prove it
- If the stat is S30, I+/I− must be landed and the furnace must be on the equipment list.
- E105 with a 24V stat = data wires on the RS terminals.
Do not
- Do not land Y on I+.
- ML196 / EL196E / EL296E are 24V unless the silk actually has iComfort.
I+ / I− are the published iComfort terminals.