ComfortBridge modulating furnace
1 / 2 · percent fire
AMVM97 / GMVM97 / ARVM97 / DM97MC. Same 1/2 pair as two-stage ComfortBridge. Capacity is 0–100%, not W1/W2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC120V
- 2Call. Data pair or 24V W → IFCBus or 24V
- 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
- 4Ignite. IFC → HSI → valve120V igniter
- 5Blow. IFC → serial ECMNo tap, no cap
Communicating modulating
ComfortBridge / ComfortNet indoor with a modulating valve.
Modulating IFC
No W2 high-fire prove. Percent request on the bus.
- 1DataData
- 2DataData
- R24V24V
- CCommon24V
Landing
- DataControlIFC 1/2outdoor 1/2
Data. Fire rate is serial.
IFC harness — modulating
Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.
Transformer + fuse
24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.
- L1 / N120VLine
- R / C24V strip24V
- FUSEOn the IFC24V
24V safety chain
Limit / rollout / door still open the heat path. Codes are on THIS IFC language.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Variable inducer + pressure band
Inducer ramps to a pressure band. There is no discrete 32 / E9 high-fire switch.
- INDVariable inducer from the IFCLine
- BANDPressure transducer / band — not LPS vs HPS24V
HSI + modulating valve
Capacity is a percent on the bus. There is no W2 solenoid to chase.
- HSI120V igniterLine
- VALVE %Serial / percent valve24V
- FLAMEµA DC24V
Serial variable-speed ECM
IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.
- SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
- CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V
Landing
- LineCallIFCinducerprove
Band, not a single PS
- LineIFCHSIvalve
120V igniter, 24V or serial valve
- 24VFlame rodIFC
µA DC
- DataIFCserial blower
No F-taps. No PSC cap.
Prove it
- CoolCloud / Daikin One shows percent capacity, not Ht1/Ht2.
Do not
- Do not apply AR9T96 / AMVC96 two-stage staging tests.
- Do not land W on a random terminal to force it.
Same published 1/2 pair. The valve is the difference.