Procedures
Heat7 min

Gas furnace sequence

If you do not know the sequence you will replace a good board. Watch the LEDs and time it.

Typical induced-draft sequence

  • Thermostat W. Inducer starts. Pressure switch closes.
  • Hot surface ignitor warms (or spark). Gas valve opens. Flame sense proves.
  • Blower starts after the OEM heat-on delay. On shutoff, gas valve first, then blower after heat-off delay.

Where it dies

  • No inducer: 120 V at the inducer, door switch, board output.
  • Inducer on, no ignition: pressure switch tubing, flue, switch ohms, ignitor amps / ohms.
  • Ignition then drop: flame sensor (clean with a non-scratch pad, not sandpaper), polarity, ground, gas pressure.
  • Limit trip: airflow, dirty filter, A-coil, overfire, or a failed limit.

Combustion

  • Manifold pressure on high and low fire vs rating plate. Clock the meter if input is in doubt.
  • CO in the flue and in the occupied space. If ambient CO is up, shut it down.